Linear smoke detector ipdl 52m. Smoke detector - adjustment

IP212-52M - single-position linear detectors, consisting of a transceiver and a reflector reflector. In the transceiver, the optical channels are separated and isolated in a two-chamber optical system.

As a reflector-reflector IP212-52M uses a high-performance reflector (reflector), capable of performing its functions even when its surface deviates relative to the optical beam by ±10 - 15 degrees.

Operating principle:

The principle of operation of the detectors is based on the property of reducing the power of an optical beam that has passed through a smoky environment. The detector's transmitter generates periodic bursts of infrared pulses.

A significant difference in the operation of two-position and single-position detectors is that in the first case the optical beam overcomes the controlled space once, and in the second case it needs to do this twice. As a result, the attenuation of the received signal for the same smoke level for the second case will be much greater, which makes it possible to set guaranteed-distinguishable response thresholds with a shorter interval. Depending on the size of the protected premises or other features of the application, IP212-52M can be set to four response thresholds (50%, 40%, 30% and 20%).

The consumption of detectors is minimized through the use of original solutions for synchronizing the operation of the receiver and transmitter (for IP212-52M - no more than 1.5 mA), which allows them to be used with control panels in a two-wire connection. The IP212-52M detectors make it possible to connect almost any fire and security devices with both alternating and unipolar voltage to the loops.

In IP212-52M, only the forced synchronization mode is always used (by default, as it is many times more noise-resistant).

On the rear side of the transceiver housing there are terminal blocks for external connections, as well as a program switch for the detector operation tactics.

The IP212-52M detectors include remote devices UV-PRD-PRM, the appearance of which is shown in the figure.


Specifications:

Parameter

Meaning

Set thresholds: for IP212-52M

20%, 30%, 40%, 50%

Range of controlled distances

from 8 to 100 m

Maximum width of space protected by one detector

no more than 9 m

Room area protected by one detector

no more than 900 m2

Supply voltage for detectors (receiver, transmitter and transceiver)

10 to 30 V

Current consumed by the detectors in the "Normal" mode: IP212-52M

no more than 1.5 mA

Current consumed by the transmitter when powered from a separate source (in any mode of operation)

no more than 1 mA

The current consumed by the receiver in the modes:
- formation of the output signal "Attention"
- formation of the output signal "Fire"
- formation of the output signal "Fault" in the "Relay" mode
- formation of the output signal "Fault" in the "Key" mode

no more than 11 mA
no more than 35 mA
no more than 11 mA
no more than 1.5 mA

The magnitude of the current jump during the formation of the signal "Attention"

Leakage current when powered by reverse polarity voltage

no more than 2 uA

Power off duration for reset

at least 2 s

The response time of the detector:
typical
maximum

5 s
10 s

The inertia of fixing the notice "Fault" in the modes:
"Fault - memory", "Fault - tolerance"
"Fault Is a Beam"
"Fault - synchronization", "Fault - failure"
"Fault - excess", "Fault - decrease"

3 to 5 s
2±0.5 s
from 40 to 70 s
from 40 to 70 s

The value of the resistance of the closed contacts of the opto-relay:
typical
maximum

15 ohm
25 ohm

The value of the resistance of the open contacts of the opto-relay

not less than 500 kOhm

The value of the insulation resistance of the output opto-relay circuits from the power supply circuits of the detector

not less than 500 kOhm

Current switched by opto-relay outputs

no more than 100 mA

Voltage switched by opto-relay outputs

no more than 100 V

Sensitivity Compensation Limit

Compensation rate:
in quick compensation mode
in slow compensation mode

0.12%/min
0.03%/min

Overall dimensions of the transceiver:
without adjusting device
with adjustment device

no more than 140x135x70 mm
no more than 185x150x140 mm

Transceiver weight:
without adjusting device
with adjustment device

no more than 0.4 kg
no more than 0.6 kg

Overall dimensions of remote devices UV-PRD-PRM

no more than 55x55x21 mm

Weight UV-PRD-PRM

no more than 0.04 kg

Overall dimensions of reflector-reflector IP212-52M

no more than 246x210x13 mm

Mass of reflector-reflector IP212-52M

no more than 0.25 kg

Operating temperature range

from minus 30 to + 55°C

Maximum Permissible Relative Humidity

Maximum allowable vibration frequency

Maximum allowable illumination at the installation site

The degree of rigidity in terms of resistance to EMF

fourth

The degree of protection of the shell in accordance with GOST 14254

Advantages of buying in TD Aktiv-SB:

Information about the technical characteristics, scope of delivery and appearance of the goods is for reference only and is based on the latest information available at the time of publication.

Designed to detect fires accompanied by the appearance of smoke, and transmit the signal of the alarm message "Fire" or "Attention" to control panels; for use in rooms with a large area, large length or high ceilings.

Peculiarities

The detector can be connected to the control panel using either a two-wire or a four-wire alarm loop.

Additional Information

The detector is designed for continuous round-the-clock operation and is used in enclosed spaces of residential and industrial buildings and structures in conjunction with fire control panels (for example, PPK-2, PPK-2M, Raduga, Signal-20P, etc.) and with security and fire control panels (for example, "Akkord", "Nota", "Signal-20", "Signal-VK", "VERS", "Granit", "Vista", etc.).

The principle of operation of the detector is based on the property of reducing the intensity of an optical beam that has passed through a smoky environment. IP212-52M operates in the infrared wavelength range. During installation, the transceiver and reflector-reflector are located opposite each other and adjusted in order to achieve maximum coincidence of the transceiver's radiation pattern with the direction to the reflector. When operating in the normal mode, the transceiver periodically (with an interval of 350 ms) generates bursts of infrared pulses (IR pulses), which, having passed through the controlled environment, reflected from the reflector and again overcome the controlled distance, return to the transceiver, are received and processed by him.

The decision about the presence of smoke in the protected space is made when the intensity of the optical beam decreases to a threshold value (relative to the intensity of the optical beam in a smoke-free environment). The trigger threshold can be selected by setting the operation tactics to 20%, 30%, 40% or 50%. Due to the fact that the beam crosses the controlled space twice, the decrease in beam intensity in percentage terms will be greater than the threshold value and will be: 36% for the 20% threshold, 49% for the 30% threshold, 64% for the 40% threshold and 75% for the 50% threshold. If the beam intensity decreases by more than 98% (corresponds to the threshold of 86%), the notification "Fault-beam" will be recorded.

Linear smoke detector 8-80m

IP212-52M - single-position linear detectors, consisting of a transceiver and a reflector reflector. The appearance of the transceiver is shown in Figure 1. In the transceiver, the optical channels are separated and isolated in a two-chamber optical system.
As a reflector-reflector IP212-52M uses a high-performance reflector (reflector), capable of performing its functions even when its surface deviates relative to the optical beam by ±10 - 15 degrees. The appearance of the reflector-reflector is shown in Figure 2.
On the rear side of the transceiver housing there are terminal blocks for external connections, as well as a program switch for the detector operation tactics (see Figure 3).
The IP212-52M detectors include remote devices UV-PRD-PRM, the appearance of which is shown in Figure 4.
IP212-52M detectors include remote devices UV-PRD-PRM. The design and appearance of remote devices is shown in the figure.
Operating principle

The principle of operation of the detectors is based on the property of reducing the power of an optical beam that has passed through a smoky environment. The detector's transmitter generates periodic bursts of infrared pulses.

A significant difference in the operation of two-position and single-position detectors is that in the first case the optical beam overcomes the controlled space once, and in the second case it needs to do this twice. As a result, the attenuation of the received signal for the same smoke level for the second case will be much greater, which makes it possible to set guaranteed-distinguishable response thresholds with a shorter interval. Depending on the size of the protected premises or other features of the application, IP212-52M can be set to four response thresholds (50%, 40%, 30% and 20%).
The consumption of detectors is minimized due to the use of original solutions for synchronizing the operation of the receiver and transmitter (for IP212-52M - no more than 1.5 mA), which allows them to be used with control panels in a two-wire connection. The IP212-52M detectors make it possible to connect almost any fire and security devices with both alternating and unipolar voltage to the loops.
In IP212-52M, only the forced synchronization mode is always used (by default, as it is many times more noise-resistant).
Technical specifications

Parameter Meaning
Set thresholds: for IP212-52M20%, 30%, 40%, 50%
Range of controlled distancesfrom 8 to 100 m
Maximum width of space protected by one detectorno more than 9 m
Room area protected by one detectorno more than 900 m2
Supply voltage for detectors (receiver, transmitter and transceiver)10 to 30 V
Current consumed by the detectors in the "Normal" mode: IP212-52Mno more than 1.5 mA
Current consumed by the transmitter when powered from a separate source (in any mode of operation)no more than 1 mA
The current consumed by the receiver in the modes:
- formation of the output signal "Attention"
- formation of the output signal "Fire"
- formation of the output signal "Fault" in the "Relay" mode
- formation of the output signal "Fault" in the "Key" mode
no more than 11 mA
no more than 35 mA
no more than 11 mA
no more than 1.5 mA
The magnitude of the current jump during the formation of the signal "Attention"7.5±0.75mA
Leakage current when powered by reverse polarity voltageno more than 2 uA
Power off duration for resetat least 2 s
The response time of the detector:
typical
maximum
5 s
10 s
The inertia of fixing the notice "Fault" in the modes:
"Fault - memory", "Fault - tolerance"
"Fault Is a Beam"
"Fault - synchronization", "Fault - failure"
"Fault - excess", "Fault - decrease"
3 to 5 s
2±0.5 s
from 40 to 70 s
from 40 to 70 s
The value of the resistance of the closed contacts of the opto-relay:
typical
maximum
15 ohm
25 ohm
The value of the resistance of the open contacts of the opto-relaynot less than 500 kOhm
The value of the insulation resistance of the output opto-relay circuits from the power supply circuits of the detectornot less than 500 kOhm
Current switched by opto-relay outputsno more than 100 mA
Voltage switched by opto-relay outputsno more than 100 V
Sensitivity Compensation Limit3 dB (50%)
Compensation rate:
in quick compensation mode
in slow compensation mode
0.12%/min
0.03%/min
Overall dimensions of the transceiver:
without adjusting device
with adjustment device
no more than 140x135x70 mm
no more than 185x150x140 mm
Transceiver weight:
without adjusting device
with adjustment device
no more than 0.4 kg
no more than 0.6 kg
Overall dimensions of remote devices UV-PRD-PRMno more than 55x55x21 mm
Weight UV-PRD-PRMno more than 0.04 kg
Overall dimensions of reflector-reflector IP212-52Mno more than 246x210x13 mm
Mass of reflector-reflector IP212-52Mno more than 0.25 kg
Operating temperature rangefrom minus 30 to + 55°C
Maximum Permissible Relative Humidity98%
Maximum allowable vibration frequency55 Hz
Maximum allowable illumination at the installation site12,000 lux
The degree of rigidity in terms of resistance to EMFfourth
The degree of protection of the shell in accordance with GOST 14254IP40

Adjustment

The adjustment process is similar to the process described for IP212-52. The choice of tactics for the detectors IP212-52M is similar to IP212-52 but has its own differences. General and individual settings of the detectors operation tactics are given in the table.

engine number
switch
Detector operation mode
Disabled (OFF) Enabled (ON)
General settings
1 Regular mode of operationAdjustment mode
2 Output signal generation mode "Fire"Output signal generation mode "Attention"
4 Quick Sensitivity Compensation ModeSlow Sensitivity Compensation Mode
Installations for IP212-52
3 Self-synchronization mode (by beam)Forced synchronization mode (via communication line)
5 Threshold
50% ("6"-OFF)
Threshold
37% ("6" - OFF)
6 Threshold
50% ("5" - OFF)
Threshold
25% ("5" - OFF or ON)
Installations for IP212-52M
3 Output "Fault-relay"Output "Fault-Key"
5 Threshold
50% ("6"-OFF)
30% ("6"-ON)
Threshold
40% ("6"-OFF)
20% ("6"-ON)
6 Threshold
50% ("5"-OFF)
40% ("5"-ON)
Threshold
30% ("5"-OFF)
20% ("5"-ON)

To facilitate the adjustment process, it is recommended to use service equipment tester IPDL-52.
Delivery set of the detector IP212-52M with a range of 8 to 80 m

Note. The ceiling bracket is not included in the main set and is supplied by separate order.

FIRE ALARMS \ Fire detectors
Linear optical smoke detector, single-position, range from 8...80 m, 2 switching schemes: powered by an alarm loop and from a separate power source, 3 output relays (FIRE-NC, FIRE-NO, FAULT-NC), U-supply 10...30V, I-cons. 1.5 mA, IP40, t-work.-30...+55°C, 185x150x140 mm (with adjustment device).

IP212-52M - single-position linear detectors, consisting of a transceiver and a reflector reflector. The appearance of the transceiver is shown in Figure 1. In the transceiver, the optical channels are separated and isolated in a two-chamber optical system.

As a reflector-reflector IP212-52M uses a high-performance reflector (reflector), capable of performing its functions even when its surface deviates relative to the optical beam by ±10 - 15 degrees. The appearance of the reflector-reflector is shown in Figure 2.

On the rear side of the transceiver housing there are terminal blocks for external connections, as well as a program switch for the detector operation tactics (see Figure 3).

The IP212-52M detectors include remote devices UV-PRD-PRM, the appearance of which is shown in Figure 4.

IP212-52M detectors include remote devices UV-PRD-PRM. The design and appearance of remote devices is shown in the figure.

Operating principle

The principle of operation of the detectors is based on the property of reducing the power of an optical beam that has passed through a smoky environment. The detector's transmitter generates periodic bursts of infrared pulses.

A significant difference in the operation of two-position and single-position detectors is that in the first case the optical beam overcomes the controlled space once, and in the second case it needs to do this twice. As a result, the attenuation of the received signal for the same smoke level for the second case will be much greater, which makes it possible to set guaranteed-distinguishable response thresholds with a shorter interval. Depending on the size of the protected premises or other features of the application, IP212-52M can be set to four response thresholds (50%, 40%, 30% and 20%).

The consumption of detectors is minimized through the use of original solutions for synchronizing the operation of the receiver and transmitter (for IP212-52M - no more than 1.5 mA), which allows them to be used with control panels in a two-wire connection. The IP212-52M detectors make it possible to connect almost any fire and security devices with both alternating and unipolar voltage to the loops.

In IP212-52M, only the forced synchronization mode is always used (by default, as it is many times more noise-resistant).

Technical specifications

Parameter

Meaning

Set thresholds: for IP212-52M

20%, 30%, 40%, 50%

Range of controlled distances

from 8 to 100 m

Maximum width of space protected by one detector

no more than 9 m

Room area protected by one detector

no more than 900 m2

Supply voltage for detectors (receiver, transmitter and transceiver)

10 to 30 V

Current consumed by the detectors in the "Normal" mode: IP212-52M

no more than 1.5 mA

Current consumed by the transmitter when powered from a separate source (in any mode of operation)

no more than 1 mA

The current consumed by the receiver in the modes:
- formation of the output signal "Attention"
- formation of the output signal "Fire"
- formation of the output signal "Fault" in the "Relay" mode
- formation of the output signal "Fault" in the "Key" mode

no more than 11 mA
no more than 35 mA
no more than 11 mA
no more than 1.5 mA

The magnitude of the current jump during the formation of the signal "Attention"

Leakage current when powered by reverse polarity voltage

no more than 2 uA

Power off duration for reset

at least 2 s

The response time of the detector:
typical
maximum

5 s
10 s

The inertia of fixing the notice "Fault" in the modes:
"Fault - memory", "Fault - tolerance"
"Fault Is a Beam"
"Fault - synchronization", "Fault - failure"
"Fault - excess", "Fault - decrease"

3 to 5 s
2±0.5 s
from 40 to 70 s
from 40 to 70 s

The value of the resistance of the closed contacts of the opto-relay:
typical
maximum

15 ohm
25 ohm

The value of the resistance of the open contacts of the opto-relay

not less than 500 kOhm

The value of the insulation resistance of the output opto-relay circuits from the power supply circuits of the detector

not less than 500 kOhm

Current switched by opto-relay outputs

no more than 100 mA

Voltage switched by opto-relay outputs

no more than 100 V

Sensitivity Compensation Limit

Compensation rate:
in quick compensation mode
in slow compensation mode

0.12%/min
0.03%/min

Overall dimensions of the transceiver:
without adjusting device
with adjustment device

no more than 140x135x70 mm
no more than 185x150x140 mm

Transceiver weight:
without adjusting device
with adjustment device

no more than 0.4 kg
no more than 0.6 kg

Overall dimensions of remote devices UV-PRD-PRM

no more than 55x55x21 mm

Weight UV-PRD-PRM

no more than 0.04 kg

Overall dimensions of reflector-reflector IP212-52M

no more than 246x210x13 mm

Mass of reflector-reflector IP212-52M

no more than 0.25 kg

Operating temperature range

from minus 30 to + 55°C

Maximum Permissible Relative Humidity

Maximum allowable vibration frequency

Maximum allowable illumination at the installation site

The degree of rigidity in terms of resistance to EMF

fourth

The degree of protection of the shell in accordance with GOST 14254


Adjustment

The adjustment process is similar to the process described for IP212-52. The choice of tactics for the detectors IP212-52M is similar to IP212-52 but has its own differences. General and individual settings of the detectors operation tactics are given in the table.

Turned off (OFF)

Included (ON)

Regular mode of operation

Adjustment mode

Output signal generation mode "Fire"

Output signal generation mode "Attention"

Quick Sensitivity Compensation Mode

Slow Sensitivity Compensation Mode

Self-synchronization mode (by beam)

Forced synchronization mode (via communication line)

Threshold
50% ("6"-OFF)

Threshold
37% ("6" - OFF)

Threshold
50% ("5" - OFF)

Threshold
25% ("5" - OFF or ON)

Output "Fault-relay"

Output "Fault-Key"

Threshold
50% ("6"-OFF)
30% ("6"-ON)

Threshold
40% ("6"-OFF)
20% ("6"-ON)

Threshold
50% ("5"-OFF)
40% ("5"-ON)

Threshold
30% ("5"-OFF)
20% ("5"-ON)

engine number
switch

Detector operation mode

General settings

Installations for IP212-52

Installations for IP212-52M

Delivery set of the detector IP212-52M with a range of 8 to 80 m

Name Quantity
Linear fire detector IP212-52M (IPDL-52M) consisting of:
Transceiver1
Reflector-reflector1
Accessory set:

UV-PRD-PRM

Wall bracket

Ceiling bracket1 (see note)
Holder1
Bolt 5X16 GOST 7805-704
Bolt 5X35 GOST 7805-702
Washer 5.10.016 GOST10450-786
Mounting kit1
Screw 4X30 DIN 79968
Dowel 6X308
Mounting kit1
Screw 3×204
Dowel S 5×254
Manual1

Note. The ceiling bracket is not included in the main set and is supplied by separate order.